Waves Fluid Engineering designs, supplies, installs, replaces and repairs hosereel water tanks for commercial, industrial and residential buildings, built to SCDF and SS 22 requirements and supplied complete with the hose reel pump system.
A hose reel water tank is the dedicated water storage that feeds a building's hose reel system, the fixed firefighting reels installed on each floor for first-aid firefighting. Unlike a domestic water tank, it exists to hold a protected reserve of water that stays available when it is needed, which is why its capacity, inlet and pump feed are all governed by the fire code.
Waves Fluid Engineering Pte Ltd installs hosereel tanks across Singapore in HDG pressed steel, bitumen painted pressed steel and SS304 stainless steel. We handle new installations, full tank replacement, leaking panel replacement and structural repair, and because we also build pump systems, we can supply the hose reel tank and its pump set as one package from one contractor.
We work with main contractors, M&E consultants, MCSTs, building managers and factory operators, and we service tanks whichever contractor originally installed them.
It is the suction tank that supplies the hose reel pumps. Under SCDF's fire code, hose reel pumps must be fed from a suction tank or inter-connected tanks with a minimum capacity of 1,100 litres, and the tank must be automatically replenished from a town main or other reliable source through a ball valve of at least 50mm diameter. Actual tank size is set by your M&E consultant based on the building and system design.
These are the core water supply requirements that apply to a hose reel installation in Singapore. Your consultant's drawing will confirm what applies to your specific building.
Hose reel pumps must be fed from a suction tank, or inter-connected tanks, with a minimum capacity of 1,100 litres.
The tank must be automatically supplied from a town main or reliable source, controlled by a ball valve of at least 50mm diameter.
Pressed steel panel tanks for fire duties are supplied to SS 22 and in compliance with SCDF requirements.
Only under a specific condition. The fire code states that tanks supplying water for domestic purposes shall not be used as suction for hosereel installations unless arrangements are made for the domestic supply to be drawn off in a way that keeps the required hose reel water reserve preserved at all times.
Hose reel water is non-potable, so the tank is selected on durability, location and budget rather than on drinking water compliance. These are the three we install most often.
| Tank type | Standard | Best suited to | Notes |
|---|---|---|---|
| HDG pressed steel | SS 22:1979, SCDF | Outdoor and roof-level hosereel tanks | Hot-dip galvanised finish, the most common choice for hose reel and sprinkler tanks in Singapore |
| Bitumen painted steel | SS 22:1979, SCDF | Indoor plant rooms and tank rooms | Pressed metal panels with black enamel bituminous coating for internal installation |
| SS304 stainless steel | Grade 304 stainless | Exposed, corrosive or long service life installations | Higher corrosion resistance and longer life, suited to hosereel, sprinkler and fire duties |
FRP / GRP panel tanks are generally specified for potable and domestic storage rather than fire duties. If your project needs both, we install them together and keep the systems correctly separated. See the full range on our water tank installation page.
A frequent question on mixed fire protection projects, and one where getting the arrangement wrong creates a real compliance problem.
Hose reels, hydrants and external drenchers must not be connected to the sprinkler system or draw from the sprinkler water supply.
Where a hose reel and automatic sprinkler system do share the same tank, the hose reel tap-off points are positioned above, so the sprinkler reserve stays protected.
Dual-compartment tanks allow one cell to be isolated for cleaning or repair while the system stays in service.
New builds, replacements and repairs, plus the pump system that goes with the tank.
New hosereel tanks designed to your consultant's drawing, delivered to site and installed by our own team.
Ageing or leaking hose reel tanks rectified, often without rebuilding the whole tank.
The tank is only half the installation. We supply and install the pump set that draws from it.
Recent hosereel tank installations and repair works carried out by our team in Singapore.
From first call to a tested, commissioned hose reel tank.
You send the requirement or the consultant's drawing.
We assess the tank room, access route and base condition.
Written quotation with tank specification and scope.
Delivery, assembly, sealing and connection on site.
Leak test, commissioning, handover with warranty.
Hose reel systems are required across most building types in Singapore, and we install the tanks that feed them.
Everything else that goes with a fire water storage installation.
Common questions about hose reel water tanks, capacity requirements and installation in Singapore.
Send us your drawing or tell us about the building, and we will send a quotation.